地下污水处理厂变电站通风系统模拟研究

  • 打印
  • 收藏
收藏成功


打开文本图片集

关键词:地下污水处理厂;变电站;FLUENT软件;模拟;空调方案

中图分类号:X703;TM727.3 文献标识码:A 文章编号:1008-9500(2025)11-0231-03

DOI: 10.3969/j.issn.1008-9500.2025.11.072

Simulation Study on Ventilation System of Underground Sewage TreatmentPlantSubstation

GONGWenjin,YINXinglei,MALizhong,GAOWei (North China Municipal Engineering Design&Research Institute Co.,Ltd.,Tianjin3Oo381,China)

Abstract: The underground sewage treatment plant substation has asmall space and a large heat disipation capacity. Taking acertain undergroundsewage treatmentplant in Xi'ancityas an example,a mathematical modelis established using FLUENTsoftware tosmulatethe pressure field,temperature field,andvelocityfieldunderdiferentinletairtemperatures anddiferentairsupplyand exhaust ratios,and the technical and economiccomparison ofairconditioning design schemes forthree existing substations is conducted.Theresults indicatethatforunderground sewage treatment plantsubstations,the air supply to exhaust ratio should be 1.1,the operating point temperature generally increases by 3 C to5 C ,and the air age intheroomisshort.Thenorthernregion prefers theairconditioning system withallairconditioning andsewagesource heat pump,while the southern region prefers the air conditioning system with indorunit and water source multi split. Keywords: underground sewage treatment plant; substation; FLUENT software; simulation; air conditioning scheme

通风系统是地下污水处理厂不可或缺的组成部分。(剩余4301字)