换流站消防泵频繁动作故障分析及处置措施

打开文本图片集
中图分类号:TU892 文献标志码:A 文章编号:2095-2945(2025)28-0152-04
Abstract:AsanimportantpartoftheHVDCtransmissionsystem,thesafeoperationofconverterstationsisdirectlyrelated tothestabilityofthepowersystem.Inthefireprotectionsystemofconverterstations,frequentactionsoffirepumpsmaylead toincreasedequipmentloss,afectthereliablityofthefireprotectionsystem,andeventreatenthesafeoperationoftheetire convertrstation.Basedontheactualcaseoffrequentactionoffirepumpsinconverterstations,thispaperinvestigatesthe causesoffrequentactionoffirepumpsinconverterstations,includingpoorpresurestabilizingefectofsurgetanks,leakageof pipelines,largeflowofsurgepumps,andunreasonablesetingvaluesofpressresignalswitches.Inresponsetothefirepump failureproblem,measuressuchasreplacingthestabilizertankcapsule,repairingpipelineleaks,adjustingthestabilizerpumpto PLCcontrol,andoptiizingthepresuresignalswichetingswereproposedtofectivelyimprovethereliabilityandstabilityof the fire protection system.
Keywords: converter station; fire pump; pressure signal switch seting;PLC control; fire protection system
随着电力系统的快速发展,高压直流输电技术得到了广泛应用,换流站作为关键枢纽,其安全防护体系至关重要。(剩余4557字)