一起配网线路开关动作异常事件分析

打开文本图片集
(南方电网广东清远清新供电局,广东清远
关键词:开关拒动;保护测试;分布式电源
中图分类号:TM726.1 文献标志码:A 文章编号:1003-5168(2025)08-0015-04
DOI: 10.19968/j.cnki.hnkj.1003-5168.2025.08.003
Analysis of an Abnormal Action Event of Distribution Network Line Switch
WU Yingshan (Guangdong Qingyuan Qingxin Power Supply Bureau of China Southern Power Grid,Qingyuan 511873, China)
Abstract: [Purposes] In order to further improve the reliability of power supply,the measures and research directions to improve the reliability of switching operation of distribution network lines are discussed.[Methods] The trip event of a distribution network line is analyzed.The action process of the switch is identified by the protection message.The abnormal situation of the switch is demonstrated from the protection configuration principle,and the typical automatic switch protection function test is completed.[Findings] After analysis,it is found that the wide access of distributed power supply has many effects on the operation of the system,so it is necessary to study and strengthen the control;the function of distribution network device is not perfect,and the test work should be done well.[Conclusions] There are still many problems in the switch of the distribution network.For example,the external challenges are faced with the access of distributed power sources and the equipment itself may also have functional defects that are difficult to find.In the future,it is necessry to continue to study and solve measures to effectively improve the rapid recovery capacity of the distribution network.
Keywords: switch refusal; protection testing; distributed power supply
0 引言
求,是目前最先进的智能电网技术之一]。(剩余4093字)