基于响应曲面法的中空纤维膜冷却器实验研究

  • 打印
  • 收藏
收藏成功


打开文本图片集

中图分类号:TB657.5 文献标志码:A

DOI:10.13338/j.issn.1674-649x.2025.01.007

Experimental study of hollow fiber membrane cooler based on response surface methodology

JIANG Zongjin ,ZHANG Rui ,LIANG Caihang,ZHAO Yunsheng (School of Mechanical and Electrical Engineering,Guilin University of Electronic Technology, Guilin 541004,Guangxi,China)

Abstract In response to the high energy and water consumption of data centers,hollow fiber membrane chillers were used to produce chilled water for the system in order to improve the air conditioning system performance and reduce water consumption.The response surface methodology (RSM) was used to design the experimental program.Air temperature,relative humidity,air flow rate,inlet water temperature and water flow rate were selected as impact factors.And a cooling system experimental bench based on fork flow hollow fiber membrane cooler was built.The data were collated and analyzed to assess the potential impact of each impact factor on the response values,including outlet water temperature,cooling efficiency,coeficient of performance (COP) and water consumption, and their magnitude. The results show that there is a significant positive correlation between inlet water temperature and outlet water temperature.And the cooling performance of the system is optimized when the inlet water temperature is In addition,increased air flow helps to increase cooling efficiency and COP,and can effectively reduce water consumption. While increasing the water flow rate can further increase COP,it can lead to an increase in outlet water temperature and an increase in water consumption. This study provides scientific basis and theoretical support for the optimal design of air conditioning cooling system in data centers.

Keywords hollow fiber membrane cooler; data center; cooling efficiency;coefficient of performance(COP);water consumption

0引言

随着数字化时代的快速发展,数据机房的数量与规模迅速扩大。(剩余13446字)

monitor
客服机器人