某综合医院污水处理提标改造工程实例研究

  • 打印
  • 收藏
收藏成功


打开文本图片集

中图分类号:X703

文章编号:1674-6139(2025)08-0091-05

文献标志码:B

Case Study of Upgrading Sewage Treatment Systemin a General Hospital

QinFan,WangJun,Shao Jun,GuanDesai,WangBaojiao(NorthernJiangsuPeople'sHospital,Yangzhou2250O1,China)

Abstract:TheorigialsewagetreatmentfacilitiesoftehospitalinJangsuProvincehadinsuficienttreatmentcapacity,sotese agetreatmentsystemasupadedtomtthelatestenvironmentalrequirementsAfterthesecondarytreatmentprocessanddisinfection process comparison,the remodeling project adopted a combination of pretreatment + biological contact oxidation + sodium hypochlorite disinfection process for treatment,the design capacity of sewage treatment 1800m3/d .According to the test data after the completion of construction,chemical oxygen demand(COD)is 120mg/L ,biochemical oxygen demand( BOD5 )65 mg/L,suspended substances(SS) 36mg/L ,ammonia nitrogen 35mg/L , pH7.95 ,fecal coliform count <20 MPN/L,total residual chlorine 6.56mg/L ,petroleum 0.13 mg/L.Thewaterqualityisimprovedsignficantlyftertheupgrading,providingareferenceforthedesignofsimilarhospitalwastewater treatment project upgrading.

Key words:medical wastewater;biological contact oxidation;upgrading

前言

医疗污水成分复杂,含有病原体、有机物、放射性污染物等各种物质[1]。(剩余4461字)