一起主变重瓦斯保护误动作事件的处理与原因分析

打开文本图片集
摘 要:某光伏电站发生一起主变重瓦斯保护动作跳闸事件,通过故障录波图分析、主变检查和试验等,确定本次事件是一起由于储油柜金属波纹管卡涩引起的重瓦斯保护误动作事件。该文详细分析事件处理过程及事件发生的根本原因,提出防范措施,避免类似事件重复发生。
关键词:变压器;金属波纹储油柜;重瓦斯保护;防范措施;光伏电站
中图分类号:TM411 文献标志码:A 文章编号:2095-2945(2024)34-0150-04
Abstract: A tripping event occurred in a photovoltaic power station for heavy gas protection of the main transformer. Through fault recorder analysis, main transformer inspection and testing, it was determined that this event was a misoperation of heavy gas protection caused by the stuck metal bellows of the oil conservator. event The incident handling process and the root cause of the incident are analyzed in detail, and preventive measures are proposed to avoid the recurrence of similar incidents.
Keywords: transformer; corrugated metal oil conservator; heavy gas protection; precautionary measures; photovoltaic power station
主变压器是光伏电站最重要的设备之一,不仅承担着电能转换的核心任务,还是系统安全、稳定运行的重要保障,一旦发生故障,可能引起全站失电,甚至影响系统的稳定性[1]。(剩余2736字)