[摘要]某光伏发电站35 kV箱变作为光伏逆变器的并网电源,在发电站中的主要作用是对光伏逆变器发出的交流电进行升压。在运行中出现一起高压熔断器单相熔断故障,造成箱变高压熔断器套管烧毁、集电线路跳闸的事故,导致35 kV集电线路所连接的逆变器全部停运,造成了巨大的电量损失和经济损失。

[关键词]高压熔断器;箱变;跳闸

[中图分类号]TM411+.2[文献标志码]A[文章编号]1001-523X(2022)08-0138-03

Together with the Analysis of the Tripping of the High Voltage Switchgear Caused by the 35 kV Box Variable Voltage Fuse

Cheng Le,Xu Shuo,Zhou Yi-long

[Abstract]A photovoltaic power station 35 kV box boost transformer(hereinafter referred to as box transformer),as the grid-connected power supply of photovoltaic inverter,the main role in the power station is to boost the electricity emitted by the photovoltaic inverter. In operation,a single-phase fuse fault of the high-voltage fuse occurred,resulting in the burning of the casing of the box-changing high-voltage fuse and the tripping of the collector line,resulting in the suspension of all the inverters connected to the 35 kV collector line,resulting in huge power losses and economic losses.

[Keywords]high voltage fuse;box change;tripping

某光伏发电站批复装机容量为50 MW,每10台箱式升压变压器(以下简称箱变)为一回35 kV集电线路,共建设5回集电线路,每回集电线路容量为10 MW;35 kV箱变配置容量为1000 kVA,高压侧额定电压等级为37 kV,低压侧电压等级为315 V的双分裂升压箱式变压器,35 kV系统接组标号为星形(Y型),在线路非全相运行(三相电流不平衡)产生差流后高压开关柜零序过流保护会动作跳闸。(剩余4228字)